ICOM-200 / 201
Configuration 0…10V
To use the analog inputs with voltages of up to 10V DC, it is neccessary to
change the jumper configuration. Please pay attention that the keys are free and
may fall out while opening the case. To avoid this, place the device keys down on the
table and then gently pull the board out of the case.
2
Following the jumper configuration for input voltages of up to 10 V.
Analog 0 Analog 1 Analog 2 Analog 3
J11 J12 J13 J15 J14 J17 J16 J18
0-10V 1 -3 1 - 3 1 –3 1 -3 1 -3 1 -3 1 –3 1 -3
Configuration 0...20mA
The past configurations have been voltage inputs. The following configuration
makes it possible to realize current inputs.
Analog 0 Analog 1 Analog 2 Analog 3
J11 J12 J13 J15 J14 J17 J16 J18
0-20mA 1 -2 1 - 2 1 -2 1 - 2 1 - 2 1 - 2 1 - 2 1 - 2
Wilke Technology GmbH • 0241/918900 • http://www.wilke.de/[email protected] 2-17